Description | |
---|---|
Designed for installation of 230V/400V, 50Hz electricity energy meters. The sealed module of the metering part is suitable for installation of different types direct connection electricity energy metering devices. Suitable for indoor and outdoor use. Self-ventilated, moisture-proof and dust-proof. Mounting methods: on the foundation, on the wall or support. Standard color - RAL 7032. Other colors are available according to project needs. | |
Technical Parameters | |
Nominal voltage Un | 400/230V |
Insulation voltage Ui | 400V |
Nominal current In | ≤ 100A |
Short-time withstand current lcw | ≤ 10kA |
Nominal frequency f | 50 Hz |
Ambient temperature | -35 to +35°C |
Degree of protection | IP44 |
Mechanical impact | IK08 |
Door opening angle | 120° |
Construction Material Coating | |
Frame, doors | Galvanized sheet steel DX51+AZ150, t=1.5mm, Powder painting: RAL 7032, ≥ 80μm |
Base | Sheet steel S235, t=2.5mm, Hot-dip zinc coating, ≥ 70μm |
Dimensions (height/width/depth in mm) | |
EAS 2/1-1F | 385 / 260 / 185 |
EAS-2/1-3F | 460 / 340 / 185 |
EAS-2-1F | 500 / 340 / 185 |
EAS-2-3F | 600 / 450 / 185 |
EAS-4-1F | 700 / 450 / 185 |
EAS-4-3F | 1000 / 600 / 185 |
EAS-6-1F | 750 / 600 / 185 |
EAS-6-3F | 1000 / 800 / 185 |
EAS-9-1F | 1000 / 800 / 185 |
Insert part height | 600 |
The height of the base | 1000 |
Standards | |
IEC/EN 61439-1, IEC/EN 61439-5, IEC/EN 60529, IEC/EN 62262, LST EN 10346, LST ISO 1461 |