Power factor correction cabinets (low voltage)

RGK1-LV

Description
Many electrical devices, equipment, and systems need an electromagnetic field for their standard operation. This leads to the consumption of reactive power, which provides basic function but not active power. The transmission and distribution system is loaded with this reactive power, making it an inefficient use of energy. The solution is to use low-voltage power factor compensation (RGK-LV) to provide the required reactive power from power capacitors directly to the appliance to avoid undesired load on the mains network.
Function
Increase energy efficiency.
Extend the service life of motors and transformers.
Balance grid and reduce reactive energy costs.
Types
RGKJ – No increased harmonic levels in the network, in simple objects.
RGKJ-H – Increased harmonic levels in the network, mainly in industrial facilities. Harmonic filters are installed, and depending on the level of harmonics in the network, 5.7%, 7%, and 14% power shift correction filters (detune filters) can be used.
RGKJ-G-H – High-speed thyristor control to handle rapidly changing network parameters.
Technical Parameters
Nominal voltage Un≤ 690V
Insulation voltage Ui1000V
Nominal current In≤ 2500A
Reactive power P12.5 kVAr - 1000 kVAr
Degree of protectionIP20…IP55
Mechanical impactIK08
Door opening angle160°
Complete Set
Circuit breaker with shunt release
PFC controller
Protection for each step
Contactors
Harmonic filters
Capacitors
Enclosure with smoke detector
Construction Material
Frame, doorsGalvanized sheet steel DX51+AZ150, t=1.5mm
BaseGalvanized sheet steel DX51+AZ150, t=2.5mm
Coating
Standard color - RAL 7035, ≥ 80μm
Other colors available according to project needs.
Standards
IEC/EN 61439-1, IEC/EN 61439-2, IEC/EN 60529, IEC/EN 62262